C SERIEST E C H N I C A L SALES GUIDECapacity Range:60~1216KWT1/R410A/50Hz/60Hz
6The units can operate with a leaving chilled fluid temperature from of20℉ to 60℉(-6℃ ~16℃) A glycol solution is required when leaving chilled fluid
INSTALLATION77.1 Dimensionsa、Graph for the shape and dimensions for LSQWRF65MG/NaC-M, LSQWF65MG/NaC-M, LSQWRF80MG/NaC-M,LSQWF80MG/NaC-M,LSQWRF65MG/NaC
7.2 Rigging InstructionCaution Guard bars are slightly longer than size of the unit Soft Material Protection Block Hoisting Hole Position Strict insp
7.3 Mounting LocationModelABCD2265 1650 1100 2200 LSQWRF65MG/NaC-MLSQWF65MG/NaC-MLSQWRF80MG/NaC-MLSQWF80MG/NaC-MLSQWRF130MG/NaC-MLSQWF130MG/NaC
Unit Model8ELECTRICAL DATAPower cable specifications and air switch types in the following list are recommended for selection.Air switch capacityMin.
Air-Cooled Scroll Chiller Technical Sales Guide GREE Central Air Conditioners15 9.2 WIRING FOR EXTERNAL CONTROL USERS Connection for External Control
16GREE Central Air Conditioners10MICROPROCESSOR CONTROLLER9.3. The Modules are connected as follow:L1 L2 L3 N 8 9XT1XT2Left Electric Box380V 3N~ 50Hz
Air-Cooled Scroll Chiller Technical Sales Guide GREE Central Air Conditioners176. System Safeties: Shall cause individual compressor systems t
18GREE Central Air Conditioners1111.1Operation ViewPowerRunError On/offResetExitConfirmXXXX-XX-XX XX:XXC Series ChillerCool【Heat/Defrost】 【Manual/Ti
Air-Cooled Scroll Chiller Technical Sales Guide GREE Central Air Conditioners19 User’s SetupUser’s Setup Module ViewRRun ModeStartupAuxiliary HeatMem
1.MODELS LIST 2.NOMENCLATURE
20GREE Central Air Conditioners12ACCESSORIESModelAccessories NameCooling onlyHeat pump 1234567891011SSOOSSSSOFFFFFFFFFF----Module unit wired controlle
Air-Cooled Scroll Chiller Technical Sales Guide GREE Central Air Conditioners2113APPLICATION DATAUnit LocationThe chillers are designed for outdoor
22GREE Central Air ConditionersCooler Flow Range:Chiller ratings and performance data pertain to cooling temperature rise of 10 (-12.4℃).
2NOMENCLATURELS QW R F 80 M G/Na C-H LSQWRF80MGNaWater ChillerScroll CompressorHeat Pump Default- Cooling only R-Heat pumpAir CooledNominal Cool
By using multi compressors on each chiller, unloading characteristics and part load performance are outstanding. Integrated part load
The evaporator is direct expansion, shell-and-tube type with water flowing in the baffled shell side and refrigerant flowing through
6GREE Central Air Conditioners3.4 Standard Control & Safety DevicesThe chiller's Unit Control Module is an innovative, modular micro
Package dime-nsionWidthDepthHeightGross weightmmmmmmkg1180 1180 2280 2280 1180 1180 2280 2345 2345 2345 2345 2345 2345 2345 2214
Models65 80 LSQWF_MG/NaC-FLSQWRF_MG/NaC-F130 160 65 80 130 160 ModelInput power for coolingRated heating capacityHeating input powerNoise
5PERFORMANCE CORRECTIONAmbient Temperature ℃(℉)Performance Correction Value25(77)1.101.141.171.201.231.271.311.341.371.411.0730(86)1.031.071.101.131.1