Air-Cooled Scroll Chiller Technical Sales Guide
GREE Central Air Conditioners
17
6. System Safeties: Shall cause individual compressor systems to perform auto shut down.
Manual reset required after the third trip of low pressure switch in 60 minutes. Manual reset
required after every trip. Includes: high discharge temperature, high pressure switch.
Compressor motor protector shall protect against damage due to high input current or
thermal overload of windings.
7. Unit Safeties: Shall be automatic reset and cause compressors to shut down if low leaving
chilled liquid temperature, and flow switch operation. Contractor shall provide flow switch
and wiring per chiller manufacturer requirements.
8. Alarm Contacts: low leaving chilled liquid temperature, high discharge temperature, high
pressure, low pressure.