GREE Central Air Conditioners
10
MICROPROCESSOR CONTROLLER
9.3. The Modules are connected as follow:
L1 L2 L3 N 8 9
XT1
XT2
Left Electric Box
380V 3N~ 50Hz 380V 3N~ 50Hz
L1 L2 L3 N
XT1
380V 3N~ 50Hz
B
A
RS232/485
10 L1 L2 L3 N
XT1
8 9
XT2
10 8 9
XT2
10
Buiding control
system
130/160 Electric Box
Main Board
PC
CN25
CN15
CN33
CN25
CN15
CN33
CN25
CN15
CN33
CN25
CN15
CN33
CN25
CN15
CN33
L1 L2 L3 N
XT1
380V 3N~ 50Hz
8 9
XT2
10
CN25
CN15
CN33
130/160 Electric Box
80 Electric Box 65 Electric Box
Long-distance
Minitor PC
power
Connect With
Water Flow Swith
Right Electric Box
Main Board
PC
Main Board
PC
Main Board
PC
Main Board
PC
Main Board
PC
Left Electric Box
Right Electric Box
Convertor
wired
controller
CN1
CN2
Commu-
nication
Module
COM1
COM2
COM2
3. Use a 4-core(4×
25
mm
95
mm ) wires to connect each module terminal XT1 L1,L2,L3,N
together.Referrence
4.130/160means:
LSQW(R)F160MG/NaC-MLSQW(R)F130MG/NaC-FLSQW(R)F160MG/NaC-F;
means
LSQW(R)F80MG/NaC-MLSQW(R)F80MG/NaC-F;
65
means
LSQW(R)F65MG/NaC-M
LSQW(R)F65MG/NaC-F.
80
with the diagram shown above.
1.
evaporator heater, unit alarm contacts, and chiller operation from
℃)ambient. Automatic reset to normal chiller operation after power failure.
2. Software stored in non-volatile memory.
3. Liquid Crystal Display, descriptions in English, numeric data in Metric unit. Sealed keypad
with sections for On/Off Switch, Reset, Up, Down, Exit and Entry.
4. Programmable set-points (within Manufacturer limits):chilled liquid temperature set-point
and range, evaporate heater on/off temperature set-point and range, daily
schedule/holiday for start/stop.
5. Display Data: Return and leaving liquid temperatures, outdoor air temperature,
discharge temperature, suction temperature, compressor run status, fan run status, day, date
and time, compressor starts/operating hours.
Automatic control of compressor start/stop, condenser fans, evaporator pump,
5 to 115(-15 to 46
LSQW(R)F130MG/NaC-M
(two modules in each one)
( one module in each one)
( one module in each one)
to next unit
——until the
last one
2
.Use a 3-core(2×1mm )signal wires to connect the Water Flow Switch with the terminal 8,9 in one of the units.