Air-Cooled Scroll Chiller Technical Sales Guide
GREE Central Air Conditioners
21
13
APPLICATION DATA
Unit Location
The chillers are designed for outdoor installation. When selecting a site for installation,
be guided by the following conditions:
1. For outdoor locations of the unit, select a place having an adequate supply of fresh
air for the condenser.
2. Avoid locations beneath windows or between structures where normal operating
sounds may be objectionable.
3. Installation sites may be either on a roof, or on the ground.
4. The condenser fans are the propeller-type, and are not recommended for use with
duct work in the condenser air stream.
5. When it is desirable to surround the unit(s), it is recommended that the screening be
able to pass the required chiller CFM without exceeding 0.1" of water external static
pressure.
6.Recommended clearances for units are given in DIMENSIONS. When the available
space is less, the unit(s) must be equipped with the discharge pressure transducer
option to permit high pressure unloading in the event that air recirculation were to
occur.
The unit should be mounted on a flat and level foundation, ground or roof, capable of
suppo-rting the entire operating weight of the unit.. Operating weights are given in the
Dimensions.
Foundation
For ground level installations, precautions should be taken to protect the unit from
being tamp-ered by or injuring to unauthorized persons. Screws on access panels will
prevent casual tam-pering; however, further safety precautions, such as unit enclosure
options, a fencedin enclos-ure, or locking devices on the panels may be advisable.
Check local authorities for safety regu-lations.
Fluid Temperature
Maximum leaving chilled fluid temperature for unit is 59 (15℃ ). or conti-nuous
operation, it is recommended that inlet fluid temperature does not exceed 86 (30℃)
( If continuous ope-ration is required for inlet water temperature above 86 (30℃ ),
please refer to GREE factory).
Minimum leaving chilled fluid temperature for standard unit is 38 (3.3℃ ) (For lower
leaving temperature contact GREE factory).
℉ F
℉
℉
℉
Chilled Liquid Piping
The chilled liquid piping system should be laid out so that the circulating pump dis ch
arges into the cooler. The inlet and outlet cooler liquid connections are given in
Dimensions.
A. Unit shall be delivered to job site fully assembled, and charged with refrigerant and
oil by the Manufacturer.
B. Unit shall be stored and handled according to the Manufacturer’s instructions.
Delivery and Handling
Leveling Unit
Unit must be leveled when installed to ensure proper oil return to the compressors.